Pressure Range

AbsoluteDifferentialGaugeMulitvariablePneumaticRemote SealsRemote/Direct MountSafety Critical

Pressure transmitters

Multi-sensor technology for multi-variable applications.

The multiplicity of pressure transmitters and application capabilities from ABB allows you to standardize transmitter installations - plant-wide. Configuration is always easy, so that instrument integrity is maintained.

Accuracy:
0.04%, 0.075% (with turndown rations up to 100:1)

Communications:

FOUNDATION Fieldbus or MODBUS

Applications:
Control Monitoring and Safety Applications
(TÜV Approved for SIL2)

 

Differential Pressure Transmitters

Main Pressure MenuModel 265DSModel 265JSModel 264BSModel 264DFModel 264DHModel 264DS

Model 265DS

265DS is a differential pressure transmitter

Download Specification Sheet .pdf

Model 265DS is a differential pressure transmitter with a selectable maximum working pressure of up to 41MPa, 5945psi. It is a reliable sensing system using the very latest digital technologies, providing a large turn down ratio up to 100:1. The user has a comprehensive choice of sensors, as is therefore able to optimize in-use total performance and stability. Configuration is provided via local keys combined with LCD indicator or via hand held terminal or PC configuration platform.
  • Base accuracy : ±0.04%
  • Span limits – 0.05 to 10000kPa; 0.2inH2O to 1450psi
    True draft range and ultra performance transmitter
  • 5–year stability
  • Multiple protocol availability – provides integration with HART®, PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities
  • Full compliance with PED Category III
Model 265JS

265JS is a differential and absolute pressure transmitter

Download Specification Sheet .pdf

Model 265JS is a differential and absolute pressure transmitter with selectable maximum working pressure of up to 41MPa, 5945psi. It is a reliable sensor system coupled with the very latest digital technologies, providing a large turn down ratio up to 100:1. The sensor choice is comprehensive, optimizing in-use total performance and stability. Configuration is flexible via via local keys combined with LCD indicator or via hand held terminal or PC configuration platform.
  • Base accuracy : ±0.04%
  • Span limits – 0.05 to 10000kPa, 0.2inH2O to 1450psi differential pressure – 0.6 to 41MPa, 87 to 5945psia absolute pressure
  • True draft range and ultra performance dual output transmitter
  • 5–year stability
  • Multiple protocol availability – provides integration with HART®, PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities
  • Full compliance with PED category III
Model 264BS

265BS differential pressure transmitter

Download Specification Sheet .pdf

This differential pressure transmitter conforms consistantly to all requirements, offering improvements in quality, delivery and service areas. Flexible configuration facilities are provided locally via local keys combined with LCD indicator or via hand held terminal or PC configuration platform. Comprehensive sensor choice optimizes in-use total performance and stability.
  • Base accuracy : ±0.075%
  • Span limits– 0.2 to 2000kPa; 0.8inH2O to 290psi
    Reliable sensing system coupled with very latest digital technologies – provides large turn down ratio up to 100:1
  • 5–year stability
  • Multiple protocol availability – provides integration with HART®, PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities
  • Full compliance with PED Category III
Model 264DF

264DF differential pressure transmitter (fast)

Download Specification Sheet .pdf

Model 264DF is a differential pressure transmitter (fast). It has a maximum working pressure of up to 21MPa, 3045psi. It can be configured via local keys combined with LCD indicator or via hand held terminal or PC configuration platform. This transmitter forms a reliable sensing system coupled with the very latest digital technologies, providing large turn down ratio up to 100:1. Users have a comprehensive choice of sensors, which optimizes in-use total performance and stability.
  • Base accuracy : ±0.075%
  • Span limits – 0.134 to 160kPa; 0.54 to 642inH2O ; 0.27 to 160kPa abs; 2 to 1200mmHg
  • 5–year stability
  • Multiple protocol availability – provides integration with HART®, PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities
  • Full compliance with PED Category IV – suitable for safety accessory application
Model 264DH

264DH differential flange mounted pressure transmitter

Download Specification Sheet .pdf

Model 264DH is a differential flange mounted pressure transmitter with a maximum working pressure of up to 5MPa, 725psi. It comprises a reliable sensing system coupled with the very latest digital technologies, providing large turn down ratio up to 100:1. The user has a comprehensive choice of sensors, which optimize in-use total performance and stability. Configuration facilities are flexible, provided locally via local keys combined with LCD indicator or via hand held terminal or PC configuration platform.
  • Base accuracy : ±0.075%
  • Span limits – 0.27 to 2400kPa; 1.08inH2O to 348 psi
  • 5–year stability
  • Multiple protocol availability – provides integration with HART®, PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities
  • PED compliance to sound engineering practice (SEP)
     
Model 264DS

264DS differential pressure transmitter

Download Specification Sheet .pdf

Model 264DS is a differential pressure transmitter with a maximum working pressure of up to 21MPa, 3045psi. It is a reliable sensing system coupled with the very latest digital technologies, providing a large turn down ratio up to 100:1. The user has a comprehensive choice of sensors, thus optimizing in-use total performance and stability. Configuration is flexible, provided locally via local keys combined with LCD indicator or via hand held terminal or PC configuration platform.
  • Base accuracy : ±0.075%
  • Span limits – 0.134 to 16000kPa; 0.54inH2O to 2320psi ; 0.27 to 16000kPa abs; 2mmHg to 2320psia
  • 5–year stability
  • Multiple protocol availability – provides integration with HART®, PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities
  • Full compliance with PED Category IV – suitable for safety accessory application